XM3.1-915-HP
Batteries
 
 

Alarms
 

Battery
 

Batteries
Battery String Voltage 42.41 V
Battery Balancing Balanced
Balancing String String A
Battery Temperature 8 °C
46 °F
  1 2 3 Balancing
String A 14.16 V 14.17 V 14.18 V Normal
Battery Charging
Charger Mode Float
Current Charger Mode Time 874 min
Charger Current 0.07 A
Charger Current Limit 10.50 A
Charger Enable Yes
Configuration
Technician ID 0
24 Hour Battery Refresh No
Battery Model Other
Accept Voltage 2.40 V/cell
Float Voltage 2.27 V/cell
Refresh Voltage 2.45 V/cell
Battery Capacity 100 Ah
Temperature Compensation 5.00 mV/cell/°C
HP Battery Rest Mode No
Battery String Detect Auto
Number of Battery Strings 1
Heater Mat Installed No
Conductance
Last Conductance Measurement  
  Last Adjusted Conductance Measurement Manufactured Date
String A Battery 1 0 S(℧) 2022-08
String A Battery 2 0 S(℧) 2022-08
String A Battery 3 0 S(℧) 2022-08

 
Copyright © 2021 Alpha Technologies Services, Inc. - an EnerSys company
www.alpha.com   |   www.enersys.com